How to Find Leaking Tubes in a Condenser

Take the condenser off line and vacuum-test every tube with a vacuum tube leak detector (VTLD). An unstable gauge reading marks a leaking tube. Then check the tube-to-tubesheet joints with a vacuum joint leak detector (VJLD) to separate tube leaks from joint leaks.

Common causes

Condenser leaks come from two places: the tube wall or the tube-to-tubesheet joint.

  • Tube corrosion, erosion or vibration wear
  • Failed rolled or welded joints

How to diagnose

The first sign is usually in the water chemistry. Confirm the leak location with the unit off line.

  • Rising condensate conductivity or hardness points to a leak.
  • With the unit off line, test tube by tube with a vacuum tube leak detector (VTLD). An unstable gauge reading means that tube leaks.
  • Check the joints with a vacuum joint leak detector (VJLD).

How to fix it

Work through the tubesheet in a fixed order so no tube is missed. Record every result.

  1. Test every tube with the VTLD and mark the leakers.
  2. Recheck the joints of those tubes with the VJLD to tell tube leaks from joint leaks.
  3. Decide whether to plug or retube based on the number of leaks.

What to send us

Send us your tube data and Alpha's application team will recommend the right leak detection setup for your condenser.

  • Tube OD, wall thickness and number of tubes
  • Tube pitch and layout (needed for the VJLD)

Frequently asked questions

How do I find a leaking condenser tube?

With the unit off line, test each tube with a vacuum tube leak detector. An unstable vacuum reading means that tube leaks. The detector runs on compressed air.

How do I tell a tube leak from a joint leak?

First mark the leaking tubes with the VTLD. Then recheck the joints of those tubes with a vacuum joint leak detector (VJLD). The VJLD result tells you whether the leak is in the tube or at the tube-to-tubesheet joint.

Should I plug the leaking tubes or retube the condenser?

Base the decision on the number of leaks you find. Test every tube first so you have the full count before you choose between tube plugging and retubing.